Specifications
Power 24V , 100mA from VF-S11 Control Card.
LED’s 3 LED’s for status indication 
Communication Ports

COM1




COM2 

 



RJ-45 for Option Unit [TYPE-FORM : RKP001Z-0] Or

for Project Download and Firmware Up gradation (Using CMOS-232-01-00, Renu Electronics Make)


9 Pin D-Sub (2 wire RS485) Profibus – DP slave

DPV0 (Cyclic Communication) 

Isolation Isolation between communication ports and Power supply, through DC-DC coupler is 1 KV.
Isolation between communication ports (Option Port and Profibus Port), through optoisolation is 1KV for 1 min.
Profibus Baud Rate

9.6k, 19.2k, 45.45k, 93.75k, 187.5k, 500k, 1.5M, 3M, 
6M, 12M Bit/s (Autodetect)

GSD File Supplied in the Installable Software CD.
GSD File Name RENU0A0E.GSD
I/O data 100 Word Input, 100 Word Output
*Inverter ID

0 - 125 (At power ON, station number is detected

automatically)

Temperature Operating : 0o to 60o C
Storage : -20o to 80o C
Humidity 10% to 90% (Non condensing)
Certifications CE
Immunity to ESD Level 3 as per IEC 1000-4-2
Immunity to Transients Level 3 as per IEC 1000-4-4
Immunity to Radiated RF Level 3 as per IEC 1000-4-3
Immunity to Conducted RF Level 3 as per IEC1000-4-6
Emissions EN55011 CISPR A

*Note 1: Inverter ID should be unique, when there are multiple inverters connected in the network.

Note 2 : Once You install Gateway Setup Software, you will find GSD file at:
            “C:\Program Files\Gateway 3.09\GWY-5oo(Profibus Gateway)\GSD”.
This is the default path. The actual path is where the user has installed Gateway Setup Software.

Note 3 : GSD file is also provided in the CD along with the Installable software.

Note 4 : Previously the model name in GSD file was GWY-500-B. Now it is changed to GWY-XXXXX to support all the products having Profibus port.