 GWY-100 Operations

The LonWorks Gateway communicates between a LonWorks network interface on one side and various serial protocols on the other side (e.g. Modbus ASCII / RTU etc.). It allows LonWorks devices to make available their LonWorks variables for PLCs or SCADA. It also makes possible for serial device to act as a LonWorks node.
It is externally powered from 3 pin terminal block and power is isolated from both communication ports. Both the communication ports are also isolated from each other.
Microsoft Windows® based configuration software, Gateway Setup, helps the user to configure Gateway unit. ‘Configuration’ means making the Gateway unit work as per the system requirements. The complete configuration for a unit is termed as ‘Project’. Project comprises of device names, Register addresses, Conditions for block execution etc. 

Block may contain information like copy number of Words, Bits etc. from one device to other device and conditions for copy, if any. Gateway transfers data between two devices by execution of blocks.
After the Project is defined, Drivers for required devices and Project should be downloaded. Gateway can now communicate with the connected devices and transfers data between them

System requirements for Gateway Setup Software are:
Programming software is common for the entire Gateway family.
   
Windows Version   : Microsoft Windows 9x/NT/2000/XP
Processor             : PENTIUM or higher
Hard disk Space    : 5 MB or more
Mouse                  : Required
RAM                     : 16 MB or more
Display resolution  : 800 X 600 (VGA) or better
Display colors       : 16 bit color 

Other Accessories required for the GWY-100 configuration and to 
use in actual application:

1. Gateway Configuration / Connecting Cable.
2. Gateway Setup Software .
3. Devices with communication cables.
4. Network Management Tool (Lonmaker) for installation of a node and binding of network variables.

Note : GWY-100 Supports up to 62 network variables. LonWorks Wizard allows the user to configure Gateway for SNVT variables.  We welcome opportunity to develop new / customized drivers for UNVT templates.


Communication ports:
GWY-100 has two communication ports COM1 and COM2. COM1 port is compatible to RS232 / RS422 / RS485 and CMOS signal levels. The Pin-outs of these ports are as shown below :

         

                                          

*Do not use pin no. 6 of PLC1/ COM1.

Switch Settings 
There are 4 switches which decide,
Switch 1: IBM Download
Switch 2,3,4: Specific Template Selection (if applicable)
LED Status 
Service LED:-
Flashing :  Node has application but is not installed in the network. (Unconfigured node)
Solid :        Node is unconfigured and applicationless. Indicates errors detected by the neuron 
                  self test routine 
OFF :          Node is configured and installed in the network.

OK LED:-
Flashing : IBM Download mode
Solid :       PLC Communication OK
OFF :         No firmware

LON LED:-
Flashing :   Receiving frames from LonWorks network

PLC1 LED:-
Flashing :   Receiving frames from PLC1 Port