| Specifications
:- |
| Power
- |
| Power |
24V DC ±10% |
| Reverse Polarity Protection |
Yes |
| Power failure with stand time |
20 ms |
| Communication Port |
Profibus DP |
| Power disspation |
2.5 W |
Power Input
From supply voltage |
Max.100 mA (Approx.)@24VDC |
|
Digital Inputs - |
| Number of inputs |
16 |
| Number of Terminals |
48 (3 terminals / input channel) |
| Type of Terminals |
Pluggable (3.81mm pitch) |
| Rated Input Voltage |
24 VDC (Max is 30VDC) |
| Rated Input Current |
5mA @ 24 VDC |
| Input Impedance |
4.9 K |
| Logic ‘0’ Voltage |
-30 to 5V |
| Logic ‘1’ Voltage |
13 to 30V |
| Input Response time |
10mS |
|
Digital Outputs (Transistor) |
| Number of outputs |
16 |
| Number of Terminals |
32 (2 terminals / Output channel) |
| Type of Terminals |
Pluggable (3.81mm pitch) |
| Maximum Load current |
500 mA |
| Voltage drop at ON |
0.8V |
| Short circuit protection |
Yes |
| Switching frequency |
100Hz (maximum) |
Nominal Load -
Ohmic
Lamp
Inductive |
48 E, 12 W
12 W
12 VA (12 H) |
|
Isolation |
| Between channels and
Internal |
Yes (Optical Isolation) |
| Between Power and
Internal |
Yes (Inductive) |
|
Profibus Baud Rate |
Profibus Baud rate (Autodetect)
|
9.6k, 19.2k, 45.45k,
93.75k, 187.5 k, 500k, 1.5M, 3M, 6M,12M bit/s |
| Bus Protocol |
Profibus-DP |
| FREEZE compatibility |
Yes |
| SNYC compatibility |
Yes |
| Diagnostic function |
Yes |
| GSD File |
Supplied with the unit |
| BUS Address |
0 - 99 Setting through
DIP Switches |
|
Temperature |
| Operating |
0° to 60° C |
| Storage |
-20° to 80° C |
| Humidity |
10% to 90% (Non
condensing) |
| |
| Mounting |
DIN rail mounting |
| Size |
155 W x 102 H x 48 D mm |
| Immunity to ESD |
as per IEC61000-4-2 |
| Immunity to Fast
Transients |
as per IEC61000-4-4 |
| Immunity to Radiated
electromagnetic field |
as per IEC61000-4-3
|
| Immunity to Conducted
disturbances |
as per IEC61000-4-6 |
| Surge |
as per IEC61000-4-5 |
| Radiated emission |
as per EN61000-6-4 |