Better Business Through Little Attachments
>> Products > FIOD-PDP (Profibus I/O) > Basic Operations
Overview | Specifications | Operations | Models
Block Diagram
Basic Operations
Function
The FIOD-PDP adds digital capability to PLC / SCADA system on Profibus network.
It functions as a Profibus DP Slave in the network. The unit offers 16 digital inputs and 16 digital outputs. The digital inputs and outputs are isolated from the host device. The module has one Profibus DP communication port to connect to host device.

Communication with Host
FIOD-PDP module supports Profibus DP Slave Protocol. The unit supports automatic detection of baud Rate. 9.6k up to 12Mbps baud rate is supported. The unit has convenient DIP switches to configure the Address in BCD format . The unit supports FREEZE and SYNC compatibility.
Station addresses up to 99 are possible in the unit.
DIP Switch Settings


 Address is coded into BCD Format.
      X1 Switch is for Units place of address.
        X10 Switch is for Ten’s place of address.
 
X10 X1 Station Address
8 4 2 1 8 4 2 1  
Off Off Off Off Off Off Off On 01
-- -- -- -- -- -- -- -- --
Off Off On Off Off Off On On 23
-- -- -- -- -- -- -- -- --
On Off Off On On Off Off On 99

 
                                    For example :-
                                    As shown in above table for address 99
                                    Positions 1 & 8 should be on from X1 Switch.
                                    Positions 1 & 8 should be on from X10 Switch.