Function
The FIOD-PDP adds digital capability to PLC / SCADA system on
Profibus network.
It functions as a Profibus DP Slave in the network. The unit
offers 16 digital inputs and 16 digital outputs. The digital
inputs and outputs are isolated from the host device. The module
has one Profibus DP communication port to connect to host
device.
Communication with Host
FIOD-PDP module supports Profibus DP Slave Protocol. The unit
supports automatic detection of baud Rate. 9.6k up to 12Mbps
baud rate is supported. The unit has convenient DIP switches to
configure the Address in BCD format . The unit supports FREEZE
and SYNC compatibility.
Station addresses up to 99 are possible in the unit.
DIP Switch
Settings
Address is coded into BCD Format.
X1 Switch is for Units place of
address.
X10 Switch is for Ten’s
place of address.
X10
X1
Station
Address
8
4
2
1
8
4
2
1
Off
Off
Off
Off
Off
Off
Off
On
01
--
--
--
--
--
--
--
--
--
Off
Off
On
Off
Off
Off
On
On
23
--
--
--
--
--
--
--
--
--
On
Off
Off
On
On
Off
Off
On
99
For example :-
As shown in above table for address 99
Positions 1 & 8 should be on from X1 Switch.
Positions 1 & 8 should be on from X10 Switch.