FIOA Series Overview
Overview | Specifications | Operations | Applications
 
Basic FIOA Operations
FIOA 0402 U is Analog Input Output Model having 4 Universal Analog inputs and 2 Analog outputs. The Analog inputs can be Voltage (0-10V, 1-5V), Current (0–20 mA, 4–20 mA), mV
(0–100 mV, 0–50 mV), RTD ( PT 100 Alpha1 and Alpha2 constant ),
Thermocouple ( B,R,S,E,J,K,N,T ).

Each input channel can be configured independently to work as any of the above type as per configuration made in the PRIZM software. The Analog outputs can be Voltage (0–10 V) or Current (4–20 mA). Output channels also are software configurable to current or voltage.
Unit supports standard Modbus RTU (slave) protocol for communicating with master device.

Analog inputs and outputs are isolated from the communication port . The power supply is isolated from all internal circuitry. Input and Output channels of the FIOA are user configurable and any combination of input types is possible. Prizm Setup Software helps the user to configure the FIOA units and use them as per his requirements. 

System requirements for Prizm Setup Software are:

 Device 

 Minimum
IBM compatible PC with Pentium processor 266 MHz Pentium® II or higher Pentium compatible CPU
Operating System Windows® 2000 and above (except Windows® Vista)
System RAM
 
At least 64 megabytes (MB) of RAM
Hard disk 150 MB free memory space
 
VGA Monitor Color settings Resolution 800x600 with 24 bit true color
 
Mouse Microsoft® mouse or compatible pointing device
                                   

Other Items required for FIOA configuration:
1. FIOA unit                                                 
2. +24VDC regulated power supply
3. Prizm Setup Software    
4. FIOA to Device cable
5. Configuration download cable (IBM-005-H-00)

 
              Dimensions                   Pin-out of Comm. Port



All dimensions are in mm.