Basic
FIOA Operations |
FIOA-0402-U-16 is
Analog Input Output Model having 4 Universal Analog inputs and
2 Analog outputs. The ADC and DAC resolution is 16 bits.
The Analog inputs can be
Voltage ( 0-10V, 1-5V), Current (0 –20 mA, 4 – 20 mA),
mV ( 0 –100 mV, 0 – 50 mV ), RTD (
PT 100 Alpha1 and Alpha2 constant ),
Thermocouple ( B,R,S,E,J,K,N,T ).
Each input channel can be configured independently to work as
any of the above type as per configuration made in the PRIZM
software. The Analog outputs can be Voltage ( 0 – 10 V) or
Current ( 4 – 20 mA). Output channels also are software
configurable to current or voltage. Unit supports standard
Modbus RTU (slave) protocol for communicating with master
device.
Analog inputs and outputs are isolated from the communication
port . Power supply is isolated from all internal circuitry.
Input and Output channels of the FIOA are user configurable and
any combination of input types is possible. Prizm Setup Software
helps the user to configure the FIOA units and use them as per
his requirements.
System requirements for Prizm Setup Software are:
|
|
Device
|
Minimum |
|
IBM compatible PC with Pentium processor
|
266 MHz Pentium® II or higher Pentium compatible CPU |
|
Operating System
|
Windows® 2000 and above (except Windows® Vista) |
System RAM
|
At least 64 megabytes (MB) of RAM |
|
Hard disk
|
150 MB free memory space
|
|
VGA Monitor Color settings Resolution
|
800x600 with 24 bit true color
|
|
Mouse
|
Microsoft® mouse or compatible pointing device |
Other Items required for FIOA configuration:
1. FIOA unit
2. +24VDC regulated power supply
3. Prizm Setup Software
4. FIOA to Device cable
5. Configuration download cable (IBM-005-H-00) |
|
Dimensions |
Pin-out of Comm. Port |
|

All dimensions are in mm. |
 |
|
|