Automation Simplified
>> Products > Eagle > Specifications
Overview | Specifications | Operations | Applications | Supported PLCs
 
 Typical Wiring Diagram
                                                        Inputs

For Thermocouple input

For RTD Input

For Current Input 
(0-20mA or 4-20 mA)

For voltage Input 
(0-50mV or 0-100mV)

                                                        Outputs

For Current Output 
(4-20 mA)

For voltage Output 
(0-10 V DC)   

 Specifications

For Voltage inputs 
Uses 0-100 mV input range resolved in 12 bit. 
For higher input ranges, use externally calibrated shunt or contact factory
Total error: ± 0.1% of scale ± 1 bit.

For Current inputs 
Uses 0-20 mA input range with 5 ohms precision shunt resolved in 12 bit. 
Total error: ± 0.1% of scale ± 1 bit.

For RTD input
Uses 3 wire compensation technique. Current sense is 0.5mA Max. 
Power dissipated in RTD is 0.025 mV @ 100 ohms. 
Range supported: -200 to 850ºC

For Thermocouple input
Uses 0-100 mV input range resolved in to 12 bit for positive input and resolved
in 11 bit for negative inputs. 
Cold junction error is + 1º maximum and 0.5º typical. 
Total error: ± 0.5% of scale ± 1 bit + CJC error

Input Type Temperature Range 1 bit Corresponds to
J -210 to 770º C 0.43º C
K -200 to 1373º C 0.61º C
E -200 to 1000º C 0.32º C
R -50 to 1769º C 2.04º C
S -50 to 1769º C 2.31º C
B 0 to 1820º C 3.21º C
N -200 to 1300º C 0.7º C
T -200 to 400º C 0.47º C

Analog Outputs
Resolution 12 Bit
Load:
4-20 mA 
0-10 V DC  
Less than 500 ohms
Minimum 400 ohms
Temperature Drift (for Digital Count) 60 PPM

General Specifications
Power + 24V DC ± 5%, 3.5W maximum
Operating Temp. 0º to 50º C
Storage Temp. -20º to 80º C
Humidity 10% to 90% (Non Condensing)
Mounting DIN rail or back panel mounting
Dimensions
Eagle-0404, Eagle-800
Eagle-0201-0302

155 mm x 102 mm x 48 mm
94 mm x 42 mm x 47 mm
Immunity to ESD 8kV Air, 6kV contact as per IEC 61000-4-2
Transient Immunity 2kV as per IEC61000-4-4
Radiated Immunity 10V / meter as per IEC61000-4-3
Emission As per EN55011 CISPR A
Isolation Analog section isolated from digital.
No isolation between channels.
IBM Port

Connects to PC for application download or operator interface for Pass-through.

PLC Port Connects to PLC
Response Time Depends on driver (Typical 200 mSec / Channel)